Permit: T09CM00797

Parcel: 132191120


Addresses:

2345 E IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM00797

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FINAL TERMINATIONS TO 100 AMP SWITCH
12/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED CHECK #2803 FOR $150.00
12/16/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NOTES:
1) PANEL LABELING 408.4
2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
12/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK VDV CABLE IN ABOVE CEILING
OK CROSS SECTIONS AT GUTTERS/WIREWAYS
OK PACKING FOR SEALS
* 501.30 FOR ALL INTERVENING RACEWAY BONDING
12/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GUTTERS HAVE MORE THAN 31 CONDUCTORS 366.22 OR WIRE WAY 372.22
2) DERATE PER 310.5 (B)(2) FOR 41 AND ABOVE
12/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SERVICE:
1) LINE SIDE BONDING TO BE AS PER 250.102 & 250.66
2) CANNOT STACK LUGS
3) MFG CALLS FOR CABLE BRACING AT CT CAN
ROOF:
1) RECEPT COVERS TO BE AS PER 406.8
2) ISOLATE POWER CONDUCTORS THRU A/C UNITS
3) PROTECT CONDUCTORS AT FITTINGS 300.4
STORE:
1) BOXES MORE THAN 1/4" IN NON COMBUSTIBLES 314.20
2) OK TO POWER TO HOT DOG COUNTER
3) VERIFY LISTING AND LABELING OF ALL KITCHEN EQUIPMENT
12/04/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PREFAB CONNECTOR: PLEASE RAISE UP OFF OF FLOOR
2) OK POLES
3) OK WIRING AT CASH WRAP
4) VERIFY BOX FILL FOR RECESSED CAN LIGHTS
11/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK BATHROOM LIDS
2) RECESSED CAN OVERFILLED
3) GUTTERS TO BE PER 366
10/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*