Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM00797
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FINAL TERMINATIONS TO 100 AMP SWITCH |
|
12/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEIVED CHECK #2803 FOR $150.00 |
|
12/16/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NOTES: 1) PANEL LABELING 408.4 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 |
|
12/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK VDV CABLE IN ABOVE CEILING OK CROSS SECTIONS AT GUTTERS/WIREWAYS OK PACKING FOR SEALS * 501.30 FOR ALL INTERVENING RACEWAY BONDING |
|
12/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GUTTERS HAVE MORE THAN 31 CONDUCTORS 366.22 OR WIRE WAY 372.22 2) DERATE PER 310.5 (B)(2) FOR 41 AND ABOVE |
|
12/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SERVICE: 1) LINE SIDE BONDING TO BE AS PER 250.102 & 250.66 2) CANNOT STACK LUGS 3) MFG CALLS FOR CABLE BRACING AT CT CAN ROOF: 1) RECEPT COVERS TO BE AS PER 406.8 2) ISOLATE POWER CONDUCTORS THRU A/C UNITS 3) PROTECT CONDUCTORS AT FITTINGS 300.4 STORE: 1) BOXES MORE THAN 1/4" IN NON COMBUSTIBLES 314.20 2) OK TO POWER TO HOT DOG COUNTER 3) VERIFY LISTING AND LABELING OF ALL KITCHEN EQUIPMENT |
|
12/04/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PREFAB CONNECTOR: PLEASE RAISE UP OFF OF FLOOR 2) OK POLES 3) OK WIRING AT CASH WRAP 4) VERIFY BOX FILL FOR RECESSED CAN LIGHTS |
|
11/02/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK BATHROOM LIDS 2) RECESSED CAN OVERFILLED 3) GUTTERS TO BE PER 366 |
|
10/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |