Permit: T09CM00758

Parcel: 13734001A


Addresses:

1660 W VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM00758

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CORRECTIONS FROM 7/7/09
07/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH BONDING AT TRANSFORMER
2) FINISH DEVICES AND CONDUCTORS BELOW 8'
07/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSTALL DEVICES 8' AND DOWN
2) LABEL PANELS PER 210.5 (2)
3) NEED REVISED PLAN STAMP BY 3RD PARTY PLAN REVIEW
4) BOND NEUTRAL AT 75 K TRANSFORMER
06/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK STRIP LIGHTS MAKE-UP
06/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT MC INSIDE STUD CHANNEL 300.4, 330.17

OK WALLS AND HARD LIDS CASH OFFICE, COUNT OFFICE, BATHROOMS, STOCKROOM, LOUNGE, HALLWAY, MANAGER OFFICE AFTER CORRECTIONS