Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2009 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
| 10/22/2009 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) SHEET NUMBER 14 UTILITY PLAN MUST HAVE REVIEWER STAMP 2) SEWER IS INSTALLED PER SHEET 14-OK TO COVER SUBJECT TO APPROVED PLAN |
|
| 10/21/2009 | PLUMBING - SEWER HCS CONNECT | Denied | 1) NEED CITY PLAN REVIEW OF SITE UTILITY PLAN 2) CORRECT BACK PITCH, SUPPORT PIPING 3) INSTALL TRACER WIRE 4) MAKE TIE IN TO BLDG, USE APPROVED FITTINGS |