Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2009 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/13/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM #1 NOT MET. WILL REFEE AT THIS TIME |
|
| 05/12/2009 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER WALTER KOCH |
|
| 05/07/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CHASE AT BEDROOM NEEDS TO BE FIRE SEALED PER CODE R 602.1 2006 IRC |
|
| 05/06/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO CUT OUT FOR CLEANOUT ON EXTERIOR LATH AT KITCHEN 2) NEED PROTECTION PLATES ON 1" SUPPLY (WATER) LINE AT GARAGE-TOP PLATE 3) NEED PITCH ON HVAC DRAIN LINE 4) NEED TO POUR SEAL SLAB AT HALL BATH TUB SHOE 5) MASTER BEDROOM CHASE NEEDS TO BE FIRE SEALED PROPERLY 6) NEED PROTECTION PLATE ON 2" VTR LINE AT LAUNDRY ROOM TOP PLATE 7) BLOCK AT BATHROOM FOR HANDICAP 8) WATER SUPPLY TEST WITH AIR MUST BE 50 PSI FOR 15 MINUTES (MINIMUM) |