Permit: T09CM00726

Parcel: 12801005H

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T09CM00726

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/22/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/15/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV W/TEST OK
WATER PIPING OK, PLAN SPECS 3 HAMMER ARRESTORS DN STREAM OF RPA. INSTALL OR PROVIDE DOCUMENTATION.
RPA LOCATION?

NOTE: RPA SPECIFIED REQUIRES A DRAIN

NEED TO INSPECT CLOSET FLANGES AFTER FINISHED FLOOR. CLOSET BEND SHALL BE FLUSH W/TOP OF FLANGE, TOP OF FLANGE SHALL BE 1/4" ABV. FLOOR AND SECURED.
UPC 316.3.2, 704.4.4