Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/30/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE ISOLATORS AS SPECIFIED ON PLANS 2) UNIT HANGER SUPPORTS CAN NOT TOUCH STRUCTURE 4) SEAL SUPPLY DUCT TO UNITS. ALL OTHER ITEMS DATED 7-23-09 COMPLETE |
|
| 07/23/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE TAPS PER PLANS 2) PROVIDE STRAPS PER PLANS 3) INSTALL FLEX PER PLANS 4) PROVIDE MASON SPRING ISOLATORS PER PLANS 5) SEAL ALL DUCT JOINTS INCLUDING END CAPS 6) PROVIDE FILTER ACCESS 7) PVC NOT APPROVED 8) PROVIDE BALANCE DAMPERS ON OSA 9) PROVIDE 1.5 RADIUS BENDS ON FLEX 10) PROVIDE TRAP PRIMER AT COND. OPEN DRAIN |