Permit: T09CM00723

Parcel: 11711080B


Addresses:

125 E PENNINGTON ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/31/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/30/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE ISOLATORS AS SPECIFIED ON PLANS
2) UNIT HANGER SUPPORTS CAN NOT TOUCH STRUCTURE
4) SEAL SUPPLY DUCT TO UNITS. ALL OTHER ITEMS DATED 7-23-09 COMPLETE
07/23/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE TAPS PER PLANS
2) PROVIDE STRAPS PER PLANS
3) INSTALL FLEX PER PLANS
4) PROVIDE MASON SPRING ISOLATORS PER PLANS
5) SEAL ALL DUCT JOINTS INCLUDING END CAPS
6) PROVIDE FILTER ACCESS
7) PVC NOT APPROVED
8) PROVIDE BALANCE DAMPERS ON OSA
9) PROVIDE 1.5 RADIUS BENDS ON FLEX
10) PROVIDE TRAP PRIMER AT COND. OPEN DRAIN