Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM00701
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECOND LAYER OF FIRE WRAP NEEDS MORE BANDING MAX. 1 1/2" FROM EDGE AND SPACING NOT TO EXCEED 10 1/2" 2. GREASE RECEPTOR NOT INSTALLED ON EXHAUST FAN 3. NO GASKET ON EXHAUST FAN 4. SF AND EXHAUST INTERLOCK OK 5. PROVIDE SMOKE CONTAINMENT TEST 6. PROVIDE EXHAUST ACTIVATION INTERLOCK 7. PROVIDE HOOD BALANCE REPORT |