Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECOND LAYER OF FIRE WRAP NEEDS MORE BANDING MAX. 1 1/2" FROM EDGE AND SPACING NOT TO EXCEED 10 1/2" 2. GREASE RECEPTOR NOT INSTALLED ON EXHAUST FAN 3. NO GASKET ON EXHAUST FAN 4. SF AND EXHAUST INTERLOCK OK 5. PROVIDE SMOKE CONTAINMENT TEST 6. PROVIDE EXHAUST ACTIVATION INTERLOCK 7. PROVIDE HOOD BALANCE REPORT |