Permit: T09CM00695

Parcel: 11204370H

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
04/08/2011 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
03/24/2011 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection 1. SEE ALL NOTES RELATING TO YARDWATER: UNDERSIZED METER, COVERED WITHOUT INSPECTION.
07/09/2010 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) TRACER WIRE IS TO BE RUN RIGHT NEXT TO PIPING, SECURED TO THE PIPE EVERY EIGHT FEET
2) EXPOSE THE P.O.C. OF NEW PIPE TO EXISTING
3) WHERE IS THE RPPBP TO BE LOCATED ?
4) EXISTING ? METER UNDERSIZED
5) EXPOSE ALL OF THE NEW WAER PIPING FOR INSPECTION
07/08/2010 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) PLANS SHOWS NEW 1 1/4" YARD WATER TO METER
2) EXPOSE NEW YARDWATER PIPING TO P.O.C. AT EXISTING
07/07/2010 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) POST ADDRESS
2) PROVIDE INSPECTION HISTORY FOR UNDERGROUND YARDWATER PIPING
3) TEMP HOSE BIB TO HAVE AVB
4) PLANS, PERMIT AND INSPECTION HISTORY TO BE ON SITE AT ALL TIMES
5) CONTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE