Permit: T09CM00683

Parcel: 10321342A


Addresses:

2112 W GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T09CM00683

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2009 MECHANICAL - HOODS Approved PER INSP COPY
07/07/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
07/06/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*.
1) REPAIR CONDUIT TO EF
2) RAISE VENT ABOVE MVA INLET
3) PROVIDE REMOVABLE GREASE TRAP
4) PROVIDE DATA ON HEAT SENSOR AND TEST
5) SEAL ALL HOLES IN DUCT
07/02/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF FIRE WRAP OK
2) OK FOR 2ND LAYER
06/30/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) COMPLETE WELDING ON HOOD TYPE 1 DUCT
06/25/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED INSPECTION
06/24/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
STRUCTURAL MODIFICATIONS REQUIRED
06/22/2009 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
TYPE 1 DUCT TOO CLOSE TO COMBUSTIBLE MATERIALS
06/09/2009 MECHANICAL - HOODS Not ready for Inspection
05/15/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
05/14/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
05/07/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK TO PROCEED