Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T09CM00683
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 04/17/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER DETAIL 3 ON P2.1 NO SYSTEM VENT MAY BE INSTALLED IN BETWEEN THE FLOW CONTROL VENT AND THE GREASE TRAP 2. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE DOWNSTREAM OF THE TRAP BEING SERVED 3. YOU WILL BE REQUIRED TO INSTALL A 3" FLOW CONTROL |
|
| 04/15/2009 | PLUMBING - ROUGH, SOIL | Cancelled | CANCELLED PER PLUMBING CONTRACTOR RAY QUINTERO #591-7762 | |
| 04/15/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* ABS DWV UNDERGROUND OK TO COVER UP TO BRANCH FOR GREASE TRAP (NOT YET INSTALLED) |