Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/21/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT SUPPORT MC TO CONDUIT, MUST BE SUPPORTED TO STRUCTURE, PER 330 NEC 2) INTERLOCK EQUIPMENT PER WIRING DIAGRAM SHT E-3 3) NEED ROOF INSPECTION 4) GFI PROTECTION REQUIRED FOR KITCHEN 110V CONV. OUTLETS (RECEPTS) PER 210-NEC |
|
| 05/19/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/14/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT MC, FLEX, LV CABLING PER CODE. SISMEC WIRES TO BE TIED OFF BOTH ENDS 2) CEILING AT STORE FRONT AREA COVERED PRIOR TO APPROVAL |