Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM00683
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/21/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT SUPPORT MC TO CONDUIT, MUST BE SUPPORTED TO STRUCTURE, PER 330 NEC 2) INTERLOCK EQUIPMENT PER WIRING DIAGRAM SHT E-3 3) NEED ROOF INSPECTION 4) GFI PROTECTION REQUIRED FOR KITCHEN 110V CONV. OUTLETS (RECEPTS) PER 210-NEC |
|