Permit: T09CM00671

Parcel: 10601228D


Addresses:

3657 N 1ST AV


Inspection Status: Denied

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T09CM00671

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Denied

Date Description Inspector Results Comments
07/30/2009 ELECTRIC - TEMP POWER FOR TEST Denied 1. MARK EQUIPEMENT GROUDS
2. CLOSE OPEN KNOCK OUTS
3. HAVE SINGLE PHASE CIRCUITS WITH NO NEUTRALS. CHECK PROPER PHASING. INSTALL NEUTRALS OR 2 POLE BREAKERS.
4. INSTALL ALL HARD WARE FOR RECEPTACLES IN INDUSTRAL
5. STRAP EMT WITH 3' AT PANELS
6. REMOVE ALL UNUSED CONDUCTORS
7. RECALL WHEN ALL CORRECTION COMPLETE
07/30/2009 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
07/27/2009 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) NEED GFI PROTECTION ON RECEPTACLES 15 & 20 120V
2) SEAL OPEN KNOCKOUTS
3) BOND SERVICE MAST.
4) BACK FED BREAKERS TO BE SECURED TO PANEL
5) SEPERATE GROUNDS AND NEUTRALS AT PANEL "C", INSTALL GROUND BAR
6) ENSURE PANEL DIRECTORIES ARE UP TO DATE
7) STRAP EMT WITHIN 3' OF CONNECTIONS TO ENCLOSURES, BOXES, ETC...
8) HAVE APPROVED REVISED PLANS ON SITE
9) CHECK PHASING OF ALL BRANCE CIRCUITS INSTALL NEUTRALS AS NECESSARY