Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T09CM00671
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | ELECTRIC - TEMP POWER FOR TEST | Denied | 1. MARK EQUIPEMENT GROUDS 2. CLOSE OPEN KNOCK OUTS 3. HAVE SINGLE PHASE CIRCUITS WITH NO NEUTRALS. CHECK PROPER PHASING. INSTALL NEUTRALS OR 2 POLE BREAKERS. 4. INSTALL ALL HARD WARE FOR RECEPTACLES IN INDUSTRAL 5. STRAP EMT WITH 3' AT PANELS 6. REMOVE ALL UNUSED CONDUCTORS 7. RECALL WHEN ALL CORRECTION COMPLETE |
|
07/30/2009 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
07/27/2009 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) NEED GFI PROTECTION ON RECEPTACLES 15 & 20 120V 2) SEAL OPEN KNOCKOUTS 3) BOND SERVICE MAST. 4) BACK FED BREAKERS TO BE SECURED TO PANEL 5) SEPERATE GROUNDS AND NEUTRALS AT PANEL "C", INSTALL GROUND BAR 6) ENSURE PANEL DIRECTORIES ARE UP TO DATE 7) STRAP EMT WITHIN 3' OF CONNECTIONS TO ENCLOSURES, BOXES, ETC... 8) HAVE APPROVED REVISED PLANS ON SITE 9) CHECK PHASING OF ALL BRANCE CIRCUITS INSTALL NEUTRALS AS NECESSARY |