Permit: T09CM00667

Parcel: 108201000

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T09CM00667

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2009 BUILDING - FINAL Approved
03/27/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL 4" VENT @ WEST SIDE
2. YOU NEED 4 BREAKERS MAX. 20 AMP. @ SUB-PANEL

THEN I WILL TEST FOR FINAL
03/26/2009 BUILDING - FINAL Denied 1) CRAWL SPACE AND VENTILATION REQUIRED UNDER WOOD FLOOR
2) SPECIFIC DETAILED APPROVED CROSS SECTION REQUIRED TYING FTG. STEM AND FRAMING EXPOSE SECTION TO VERIFY
3) ARC FAULT PROTECTION REQUIRED IN BEDROOM OUTLETS, SWITCHES AND SMOKE ALARM
4) DEDICATED OUTLET AND CIRCUIT REQUIRED FOR WALL A/C