Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM00645
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1ST LEVEL DEMO AND CHANGES OK |
|
05/19/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 2ND LEVEL TRS OK MV VALVE AT WH OK T&P VALVE IS NOT OPERATIONAL |
|
05/14/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PETITION OF APPEAL WITH JESSE SANDERS SIGNATURE-OK 2) 3RD LEVEL FINAL OK 3) STILL NEED TO INSPECT MV AT WH LOCATION |
|
05/12/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* THIS INSPECTION FOR 3RD LEVEL FIXTURES ONLY 1. PROVIDE CORRECT CRITICAL LEVEL FOR STOOLS (2) VACUUM BREAKERS 2. PROVIDE TEMPERATURE LIMITING TO 110 DEG. AT PUBLIC USE LAVS HOT WATER 3. PROVIDE TRAP PRIMER FOR BOTH FLOOR DRAINS |
|
04/27/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE PETITION OF APPEAL SIGNED BY BUILDING OFFICIAL FOR WATERLESS URINAL USE ON THIS PROJECT ON SITE 2ND & 3RD LEVEL CAPS FOR DEMO OF LAVS & STOOLS & URINAL OK |