Permit: T09CM00645

Parcel: 13317064C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T09CM00645

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1ST LEVEL DEMO AND CHANGES OK
05/19/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
2ND LEVEL TRS OK
MV VALVE AT WH OK
T&P VALVE IS NOT OPERATIONAL
05/14/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PETITION OF APPEAL WITH JESSE SANDERS SIGNATURE-OK
2) 3RD LEVEL FINAL OK
3) STILL NEED TO INSPECT MV AT WH LOCATION
05/12/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
THIS INSPECTION FOR 3RD LEVEL FIXTURES ONLY
1. PROVIDE CORRECT CRITICAL LEVEL FOR STOOLS (2) VACUUM BREAKERS
2. PROVIDE TEMPERATURE LIMITING TO 110 DEG. AT PUBLIC USE LAVS HOT WATER
3. PROVIDE TRAP PRIMER FOR BOTH FLOOR DRAINS
04/27/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE PETITION OF APPEAL SIGNED BY BUILDING OFFICIAL FOR WATERLESS URINAL USE ON THIS PROJECT ON SITE

2ND & 3RD LEVEL CAPS FOR
DEMO OF LAVS & STOOLS & URINAL OK