07/10/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BONDING JUMPERS TO BE PER 250.66
2) NEED BONDING AT SERVICE NIPPLE 250.92
3) NEED LABELING FOR EQUIPMENT
4) PROVIDED BUSHING OR BELL ENDS 352.46 AND 300.4
06/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*