Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BONDING JUMPERS TO BE PER 250.66 2) NEED BONDING AT SERVICE NIPPLE 250.92 3) NEED LABELING FOR EQUIPMENT 4) PROVIDED BUSHING OR BELL ENDS 352.46 AND 300.4 |
|
| 06/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |