Permit: T09CM00638

Parcel: 21248069E

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM00638

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/16/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS FOR POWER RACK,
INVERTER AND DISTRIBUTION

WIRE WAY TO BE ABOVE PLUMB AND CONDUIT ENTRANCES FOR DRAINAGE COMBINER BOX RACEWAY ENTRANCES TO BE THROUGH SIDE OF WIRE WAY AND GROUNDING CONNECTIONS ABOVE MIDWAY ON SIDES - THIS IS A ONE TIME ONLY INSTALLATION METHOD.
06/08/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1 - 3" PVC VAULT TO MED VOLTAGE XFMR
OK 4 - 2" 1 - 1" 1 - 3/4" PVC RACK TO SES

*GUTTER ARE INDOOR NEMA 1 NOT OUTDOOR NEMA 3R