Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSTALL MAIN BONDING SCREW AT MAIN DISCONNECT 250.24 2) A GROUNDED CONDUCTOR IS NEEDED AT SERVICE DISCONNECT 250.24 (C) 3) RECEIVED CHECK #5068 FOR $150.00 |
|
| 05/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RACEWAYS ACCROSS ROOF 2) OK RACEWAY TO MAIN DISCONNECT 3) PLEASE PROVIDE INSTRUCTIONS FOR INSTALLATION OF ROOF MODULES |