Permit: T09CM00628

Parcel: 110052560


Addresses:

4308 E HAYHURST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/18/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) RECEIVED PETITION OF APPEAL
11/16/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SEE NOTE #1 FROM 11/10/09 AND COMPLY
11/10/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTE: ALL FUTURE INSTALLATIONS REQUIRE MINIMUM 1 1/2" FROM PIPINT OT ROOF SURFACE
1) TEMPERATURE AND PRESSURE RELIEF SHALL BE INSTALLED PER PETITION OF APPEAL LEFT ON SITE
2) PRESSURE RELIEF PIPING IS TO BE FULL SIZE TO PAN FROM DISCHARGE OPENING SIZE. TERMINATE 1" ABOVE TOP OF PAN
3) HAVE AN ELECTRICAL INSPECTION ADDED TO THIS PERMIT FOR NEW ELECTRICAL CIRCUIT AND COMPLY WITH CURRENT ELECTRICAL CODE FOR THIS INSTALLATION
4) PROVIDE A MEANS FOR ELECTRICAL DISCONNECT FOR THE WATER HEATER
5) ELECTRICAL LIST NOT COMPLETE
11/09/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/06/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*