Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED PETITION OF APPEAL |
|
| 11/16/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE SEE NOTE #1 FROM 11/10/09 AND COMPLY |
|
| 11/10/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE: ALL FUTURE INSTALLATIONS REQUIRE MINIMUM 1 1/2" FROM PIPINT OT ROOF SURFACE 1) TEMPERATURE AND PRESSURE RELIEF SHALL BE INSTALLED PER PETITION OF APPEAL LEFT ON SITE 2) PRESSURE RELIEF PIPING IS TO BE FULL SIZE TO PAN FROM DISCHARGE OPENING SIZE. TERMINATE 1" ABOVE TOP OF PAN 3) HAVE AN ELECTRICAL INSPECTION ADDED TO THIS PERMIT FOR NEW ELECTRICAL CIRCUIT AND COMPLY WITH CURRENT ELECTRICAL CODE FOR THIS INSTALLATION 4) PROVIDE A MEANS FOR ELECTRICAL DISCONNECT FOR THE WATER HEATER 5) ELECTRICAL LIST NOT COMPLETE |
|
| 11/09/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/06/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |