Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM00620
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/01/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE DUCT SMOKE DETECTOR AS PER PLANS 2. DETECTORS MUST BE CONNECTED TO FIRE ALARM SYSTEM 3. THE N.E. UNIT WILL REQUIRE A DUCT SMOKE DETECTOR NOT ON PLANS 4. EXISTING FAN COIL NEEDS A SECONDARY DRAIN PAN 5. OK FOR PARTIAL CEILING TILES |