Permit: T09CM00620

Parcel: 13507450A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00620

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/01/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE DUCT SMOKE DETECTOR AS PER PLANS
2. DETECTORS MUST BE CONNECTED TO FIRE ALARM SYSTEM
3. THE N.E. UNIT WILL REQUIRE A DUCT SMOKE DETECTOR NOT ON PLANS
4. EXISTING FAN COIL NEEDS A SECONDARY DRAIN PAN
5. OK FOR PARTIAL CEILING TILES