Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00606
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE ITEM #5 FROM PREVIOUS INSPECTION |
|
06/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLE WITH NO POWER 2. PAINTED OVER RECEPTACLES TO BE REPLACED OR PAINT REMOVED 3. ALL NEW WORK TO BE SHOWN ON PLANS. HAVE NEW TRACK LIGHT SYSTEM NOT REFLECTED ON PLANS 4. INSTALL END CAP ON TRACK LIGHT 5. CIRCUITING OF TRACK LIGHT TO BE PER NEC 220.43(B) 6. NEED NEW PANEL DIRECTORIES. HAVE PANELS OPEN FOR INSPECTION 7. NEED PROPER WORKING CLEARANCES IN FRONT OF PANELS NEC 110.26 8. OPEN CEILINGS TO SEE NEW WORK |