Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM00593
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/05/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/09/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
10/02/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
09/18/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
04/09/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO COMBUSTIBLE MATERIALS ALLOWED IN RETURN PLENUM 2. ALL PVC PIPING TO HAVE PRIMER THAT IS PURPLE IN COLOR 3. REFRIGERATION PIPING INSULATION MUST EXTEND OVER DRAIN PAN 4. C.V. STAMPS DO NOT SPAN TRUSSES PER PLANS |