Permit: T09CM00593

Parcel: 125112440


Addresses:

3727 E 5TH ST #101


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09CM00593

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/09/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CAP OFF THE VENT INSTALLED BEFORE THE TRAP ON CONDENSATE DRAIN. VENT NOT REQUIRED
2) OK FOR FINAL UNIT #101
10/02/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FOR PVC NIPPLE ON SECONDARY DRAIN
2) RTU SUPPORT SYSTEM OK TO CONTINUE
3) COPPER GLUE NOT APPROVED
09/18/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ITEMS #2 & 3 STILL NOT COMPLETE
08/17/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE A TRAP ON CONDENSATE DRAIN LINE
2) SCHEDULE 40 PVC NOT ALLOWED IN A PLENIUM. USE CPVC OR COPPER
3) ID UNITS ON ROOF WITH APT. NUMBER
4) PROVIDE INSTALL INSTRUCTIONS FOR FAN COILS
07/23/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO PROCEED
04/13/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/09/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*