Permit: T09CM00583

Parcel: 13101023B


Addresses:

1884 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM00583

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) RECEIVED SPECIAL INSPECTION REPORT FOR OUTDOOR LIGHTING COMPLIANCE
03/23/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED SPECIAL INSPECTION REPORT FOR COMPLIANCE WITH OUTDOOR LIGHTING CODE-SEE SHEET E0.2
03/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL OFFS FOR SPEAKERS
2) HAVE R/3 CORDS ON 30 AMP APPLIANCES
3) RECEPT NO POWER
4) NEED PROTECTIVE BUSHING #4 AND LARGER
5) BOND ALL INTERVENING RACEWAYS TO HAZARDOUS LOCATION
6) NEED DISCONNECT FOR FAN COIL FREEZER
7) OVERFUSED ON SMALL COOLER CONDENSOR
8) IDENTIFY DISCONNECTS
9) CHECK GROUND MAKE UP ON ICE MAKER
10) NEED SERVICE RATING LABEL PER PLANS
11) INSTALL EXTENSION RINGS ON BOXES MORE THAN 1/4" BACK
12) NEED TO HAVE OUTSIDE LIGHTS WORKING NEXT INSPECTION
03/17/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK PACKING AT SEAL OFFS