Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED SPECIAL INSPECTION REPORT FOR OUTDOOR LIGHTING COMPLIANCE |
|
| 03/23/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED SPECIAL INSPECTION REPORT FOR COMPLIANCE WITH OUTDOOR LIGHTING CODE-SEE SHEET E0.2 |
|
| 03/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL OFFS FOR SPEAKERS 2) HAVE R/3 CORDS ON 30 AMP APPLIANCES 3) RECEPT NO POWER 4) NEED PROTECTIVE BUSHING #4 AND LARGER 5) BOND ALL INTERVENING RACEWAYS TO HAZARDOUS LOCATION 6) NEED DISCONNECT FOR FAN COIL FREEZER 7) OVERFUSED ON SMALL COOLER CONDENSOR 8) IDENTIFY DISCONNECTS 9) CHECK GROUND MAKE UP ON ICE MAKER 10) NEED SERVICE RATING LABEL PER PLANS 11) INSTALL EXTENSION RINGS ON BOXES MORE THAN 1/4" BACK 12) NEED TO HAVE OUTSIDE LIGHTS WORKING NEXT INSPECTION |
|
| 03/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK PACKING AT SEAL OFFS |