Permit: T09CM00583

Parcel: 13101023B


Addresses:

1884 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/23/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/01/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CHECK PLANS TO SEE IF ALL BREAKERS IN PANEL T TO BE 65 KAIL RATED
2) NEED TO POST BOND TO GET POWER RELEASED
3) FINISH WORK IN CT CABINET
4) CONNECT IN GROUND TO PANEL T
02/22/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CEILINGS OK
2. MAKE UP IN POLE LIGHTS OK
02/16/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) USE APPROVED METHODS TO SUPPORT ELECTRIC ABOVE GRID
2) SUPPORT WIRES NEEDED FOR EXIT SIGN
3) SECURE M/C CABLE UNDER COUNTER AS PER CODE
4) PLEASE VERIFY LISTING FOR ALL EQUIPMENT
02/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CONNECTION TO CHEMICAL GROUNDING ELECTRODE
12/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/24/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*