Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/01/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CHECK PLANS TO SEE IF ALL BREAKERS IN PANEL T TO BE 65 KAIL RATED 2) NEED TO POST BOND TO GET POWER RELEASED 3) FINISH WORK IN CT CABINET 4) CONNECT IN GROUND TO PANEL T |
|
| 02/22/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CEILINGS OK 2. MAKE UP IN POLE LIGHTS OK |
|
| 02/16/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) USE APPROVED METHODS TO SUPPORT ELECTRIC ABOVE GRID 2) SUPPORT WIRES NEEDED FOR EXIT SIGN 3) SECURE M/C CABLE UNDER COUNTER AS PER CODE 4) PLEASE VERIFY LISTING FOR ALL EQUIPMENT |
|
| 02/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CONNECTION TO CHEMICAL GROUNDING ELECTRODE |
|
| 12/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |