Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T09CM00574
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2010 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
10/05/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) NEED PLANS AND PERMITS ON SITE FOR FINAL |
|
08/19/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A REFEE MAYBE ASSESSED FOR UNECESSARY INSPECTIONS 2) VERIFY MULTI-POLE LUG TERMINATIONS AT CONTACTOR 3) CIRCUIT DIRECTORY TO BE PER 408.4 4) FINISH PREVIOUS ITEM 2, 3 & 4 |
|
08/14/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FINISH MAKE UP 2) BOND ENCLOSURE 250.148 3) BOND SUPLIMENTAL GROUND 250.53 4) VERIFY 2ND GROUND ROD AND CONDUCTOR 5) NO LOAD CONNECTED AT THIS TIME |