Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00570
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/28/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING CLEARANCES A + A1 110.26 2) PANEL DIRECTORY TO BE AS PER 408.4 3) NEED ELECTRICIAN PRESENT TO OPEN PANELS 4) CANNOT TELL WHICH CIRCUIT CONTROLS HALL LIGHTS TO VERIFY 700.12 (F) 5) RECEPTACLES COVER 406.8 6) VERIFY 314.20 AT STUCCO |
|
07/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |