Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM00570
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING ELECTRIC 2) MAINTAIN WORKING CLEARANCES AT A/C'S 3) RECEPTACLE COVER TO BE PER 406.8 4) 814.20 WILL APPLY AT STUCCO |
|
07/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT M/C CABLE PER CODES 12" + 6' 2) BOXES OVER FILLED 3) LABEL A/C DISCONNECT 4) PROPERLY IDENTIFY UNGROUNDED CONDUCTORS |