Permit: T09CM00570

Parcel: 14016003F

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM00570

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/17/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK ABOVE CEILING ELECTRIC
2) MAINTAIN WORKING CLEARANCES AT A/C'S
3) RECEPTACLE COVER TO BE PER 406.8
4) 814.20 WILL APPLY AT STUCCO
07/16/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT M/C CABLE PER CODES 12" + 6'
2) BOXES OVER FILLED
3) LABEL A/C DISCONNECT
4) PROPERLY IDENTIFY UNGROUNDED CONDUCTORS