Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
Permit Number - T09CM00563
Inspection Description - MECHANICAL - HYDRONIC PIPING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2010 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* | |
| 10/13/2009 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 100 PSI HYDRO TEST ON NEXT SECTION OF PIPE 2) OK TO INSULATE 3) OK FOR FINAL SECTION TO BE TESTED UNDER LIVE PRESSURE |
|
| 10/08/2009 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO PIPING IN MECH ROOM PUMP DISCHARGE (X3) TO NEW CHILLER 12" INLET ISO VALVE AND CONDENSOR H20 SYSTEMS 100 + PSI OK |
|
| 08/31/2009 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 100 PSI HYDROSTATIC TEST ON SECTION 1 OK FOR INSULATION 2) SUPERINTENDENT CHUCK |