Permit: T09CM00563

Parcel: 11711076A


Addresses:

126 E ALAMEDA ST

Inspection Status: Approved

Inspection History: MECHANICAL - HYDRONIC PIPING

Date Description Inspector Results Comments
01/13/2010 MECHANICAL - HYDRONIC PIPING Approved IVRS - Inspection :*
10/13/2009 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI HYDRO TEST ON NEXT SECTION OF PIPE
2) OK TO INSULATE
3) OK FOR FINAL SECTION TO BE TESTED UNDER LIVE PRESSURE
10/08/2009 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) HYDRO PIPING IN MECH ROOM PUMP DISCHARGE (X3) TO NEW CHILLER 12" INLET ISO VALVE AND CONDENSOR H20 SYSTEMS 100 + PSI OK
08/31/2009 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI HYDROSTATIC TEST ON SECTION 1 OK FOR INSULATION
2) SUPERINTENDENT CHUCK