Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM00558
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED LETTER FROM ARC VISION |
|
07/20/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE BACK FLOW PROTECTION PER PLAN OR STAMPED SEALED LETTER FROM ENGINEER GIVING OK FOR USE OF CODE APPROVED BACK FLOW PROTECTION DEVICES 2) REMOVE VACUUM BREAKER FROM JANITOR SINK CHEMICAL ADDITION WATER SUPPLY |
|
05/28/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/28/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL IN 03075 WITH 03090 1. PROVIDE BACKFLOW PROTECTION PER APPROVED PLAN 2. CHEMICAL ADDITION REQUIRES CORRECT SOURCE OF WATER 3. WHERE MULTIPLE BACKFLOW DEVICES ARE LOCATED EACH SHALL BE LABELED 4. INDIRECT DRAINS TO HAVE CORRECT FALL AND AIR GAPS AS REQUIRED OF APPROVED DRAINAGE MATERIALS. |