Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) PROVIDE LETTER IF DELETING METAL DRAW BANDS 2) OK FOR CEILING TILES |
|
| 11/16/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECTIONS HAVE NOT BEEN MADE 2) NO CONTRACTOR ON SITE |
|
| 11/09/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE METAL DRAIN BANDS AS PER PLAN 2) FINISH TERMINATING DRYER VENT 3) INSULATE SUPPLY DUCT TO VAV 4) INSTALL PLUGS IN CONDENSATE CLEANOUTS 5) SEAL DUCT JOINTS AT DROPS THRU ROOF HP-5 6) INSULATE SQUARE TO ROUND ADAPTER 7) OK PARTIAL CEILING TILES |
|
| 10/20/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUSPENDED ROUGH DUCT OK TO PROCEED |
|
| 10/19/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/14/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |