Permit: T09CM00551

Parcel: 13317062G

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/19/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) PROVIDE LETTER IF DELETING METAL DRAW BANDS
2) OK FOR CEILING TILES
11/16/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECTIONS HAVE NOT BEEN MADE
2) NO CONTRACTOR ON SITE
11/09/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE METAL DRAIN BANDS AS PER PLAN
2) FINISH TERMINATING DRYER VENT
3) INSULATE SUPPLY DUCT TO VAV
4) INSTALL PLUGS IN CONDENSATE CLEANOUTS
5) SEAL DUCT JOINTS AT DROPS THRU ROOF HP-5
6) INSULATE SQUARE TO ROUND ADAPTER
7) OK PARTIAL CEILING TILES
10/20/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUSPENDED ROUGH DUCT OK TO PROCEED
10/19/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/14/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*