Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/21/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) B-VENT IS TO CLOSE TO ROOF SHEATHING, PROVIDE MINIMUM 1" CLEARANCE TO ALL COMBUSTIBLE MATERIALS 2) COMPLETE W/H FLUE PIPING 3) COMPLETE RTU INSTALLATION 4) SEAL ALL EXTERIOR JOINTS ON MVA DUCT 5) PROVIDE GASKET ON KITCHEN EXHAUST DUCT TO FAN CONNECTION 6) REMOVE ALL PAINT FROM GREASE DUCT AT FAN CONNECTION 7) DISHWASHER EXHAUST FAN WIRING NOT INSTALLED CORRECTLY 8) PROVIDE ALL TESTS, REPORTS, DOCUMENTATION REQUIRED FOR FINAL INSPECTION |