Permit: T09CM00539

Parcel: 105110630

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
07/30/2009 MECHANICAL - HOODS Approved IVRS - Inspection :*
07/09/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED FIRE WRAP AND METAL FLASHING ABOVE HOOD
2) OK TO SHEETROCK CEILING
07/08/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT
2) OK TO COMPLETE 1ST LAYER OF FIRE WRAP
07/07/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) LEAK TEST FAILED
07/06/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) WELDED DUCT NOT COMPLETE
07/02/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED LEAKS ON GREASE DUCTS, OK FOR 1ST LAYER OF FIRE WRAP
2) OK TO DBL WRAP TOP SECTION THRU ROOF ONLY
3) STILL NEED TO LEAK TEST TOP JOINT OF GREASE DUCT
06/30/2009 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE SIDE WALL NEXT TO HOOD ALSO NEEDS TO BE COVERED WITH STAINLESS
2) SHORT DUCT LEAKING AT TOP PLATE
3) LONG DUCT 1 BLOCK NEAR BOTTOM
06/29/2009 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MECHANICAL AND OR GENERAL CONTRACTOR TO BE ON SITE TO PROVIDE ALL MEANS AND MATERIALS FOR SMOKE/LIGHT TEST OF TYPE 1 GREASE DUCT