Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T09CM00519
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2010 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
04/07/2010 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* OK BOND CLAMP TO PIPE |
|
04/06/2010 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
04/01/2010 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
04/01/2010 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) WAITING ON LETTER FROM ENGINEER FOR CONDUCTORS |
|
03/29/2010 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED GROUNDED CONDUCTOR TO SERVICE DISCONNECT 250.24 (C) 2) BOND GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR AS 1ST DISCONNECTING MEANS 250.24 3) LABEL SERVICE DISCONNECT 230.70 4) TIGHTEN CONDUCTOR TERMINATIONS 5) FILL UNUSED OPENING IN METER HUB 6) CONDUCTOR COLORS TO BE PER 210.5 (C) AMENDMENTS 7) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM SWITCH BOARD 8) CORRECTLY TERMINATE ? TERMINAL LUGS AND CONDUCTOR 9) CONDUCTOR FROM DISCONNECT TO SWITCH BOARD NOT PER PLANS |