Permit: T09CM00519

Parcel: 140100110


Addresses:

3088 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T09CM00519

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2010 ELECTRIC - TEMP POWER FOR TEST Approved
04/07/2010 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
OK BOND CLAMP TO PIPE
04/06/2010 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
04/01/2010 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
04/01/2010 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) WAITING ON LETTER FROM ENGINEER FOR CONDUCTORS
03/29/2010 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED GROUNDED CONDUCTOR TO SERVICE DISCONNECT 250.24 (C)
2) BOND GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR AS 1ST DISCONNECTING MEANS 250.24
3) LABEL SERVICE DISCONNECT 230.70
4) TIGHTEN CONDUCTOR TERMINATIONS
5) FILL UNUSED OPENING IN METER HUB
6) CONDUCTOR COLORS TO BE PER 210.5 (C) AMENDMENTS
7) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM SWITCH BOARD
8) CORRECTLY TERMINATE ? TERMINAL LUGS AND CONDUCTOR
9) CONDUCTOR FROM DISCONNECT TO SWITCH BOARD NOT PER PLANS