Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM00519
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2010 | ELECTRIC - ABOVE CEILING | Approved | ||
04/13/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT VDV CABELING PER 725.24, 800.24 AND 300.11, CANNOT USE CONDUIT RACEWAY AS SUPPORT 2) FILL UNUSED RACEWAY OPENINGS 3) JUNCTION BOXES OVER FILLED 4) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 5) DISCONNECT FOR FIXTURES AS PER 410.73 6) SUPPORT CONDUITS PER CODES 7) EXPOSED CONDUCTOR BETWEEN HAND DRYER AND WALL 8) EXIT LIGHTING AND EM LIGHTS BY BACK DOOR NOT WORKING 9) LABEL A/C DISCONNECTS 10) PLEASE VERIFY INSPECTION FOR SIGN MONUMENT RACEWAY UNDERGROUND 11) OUTDOOR LIGHT FIXTURES OPEN BOXES AND EXPOSED CONDUCTOR TO WEATHER |
|
03/03/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/02/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |