Permit: T09CM00519

Parcel: 140100110


Addresses:

3088 E BENSON HY

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/28/2010 ELECTRIC - INTERMEDIATE Approved
03/03/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PANEL WALL AND HARD LID
03/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT CONDUITS ABOVE PANEL AND ABOVE CEILING HARD LID
2) OK WALLS EXCEPT AT PANEL
03/01/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT VDV CABLING PER 725.24 & 800.24
2) SECURE M/C CABLE AS PER 330.17 & 330.30
3) USE CORRECT SIZED CONDUIT STRAPS
4) BROKEN M/C ARMOR
5) BOX OVER FILLED
6) LOOSE FITTINGS
7) STRAP EMT WITHIN 3' OF BOXES, PANEL AND 10' INTERVALS
8) VERIFY VOLTAGE RATING ON CLASS 2 WIRING IN PANEL
9) FILL UNUSED OPENINGS IN BOXES
10) M/C CABLE TO TERMINATE
11) SECURELY ATTACH BOXES TO STUD
12) PLANS CALL FOR 1/0 UFER