Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INSPECTION SCHEDULED IN ERROR. CANCELLED BY BOB NOVAK |
|
| 09/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) LOOSE FITTING 2) EQUIPMENT NOT LABELED 3) RECEIVED LETTER FOR GENERATOR APPLICATION |
|
| 08/18/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/09/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND BUSHING NEEDED AT CONCENTRICS 250.97 2) LABEL ALL EQUIPMENT 3) RECEPTACLE COVER TO BE PER 406.8 4) NEED PLANS ON SITE 5) PLEASE HAVE THIRD PARTY NRTL EVACUATE DRILL AND TAPING OF LINE SIDE BOSS AT GENERATOR |