Permit: T09CM00499

Parcel: 13734001E

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00499

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/16/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/06/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
FLEX DUCTS STILL NOT PROPERLY SUPPORTED
SUPPORT EVERY 5'
CANNOT USE CONDUITS FOR SUPPORT
04/03/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDENSATE TO BE INSULATED IN WALL
2. PROVIDE FULL CROSS SECTIONAL FREE AREA OF FLEX DUCT PER PLANS
3. SEAL AND INSULATE WYE BOXES AT FLEX DUCT RUNS
4. PROVIDE PROPER SUPPORT ON FLEX DUCT SUPPORTS NOT TO EXCEED 5'
5. RETURN CAN PATCHES TO BE SEALED
6. EXHAUST DUCT DROP NOT SEALED AT END CAP
7. FLEX NOT TO BE SUPPORTED BY CONDUIT, SPRINKLER PIPE, ETC.