Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM00499
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
06/05/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ALL ITEMS FROM 6/1/09 INCLUDING STERILIZATION REPORT FOR POTABLE WATER SYSTEM & BACTERIA REPORT 2. PAINT ALL VENTS THRU ROOF TO PREVENT DAMAGE FROM SUN EXPOSURE THAT ARE PVC OR ABS NOTE: TYPICALLY DELETIONS OF PLUMBING FIXTURES REQUIRE REVISED CITY APPROVED PLANS PER NOTE #2 ON 5/6/09 AND SINK DELETION CALL IN ALL INSPECTIONS THAT HAVE NOT BEEN APPROVED |
|
06/03/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) THIRD PARTY INSPECTION REPORT ON SITE 2) COMPLETE LIST FROM 6/1/09 3) COMPLETE WATER HEATER DETAIL 4) COVER HOLE IN ? SINKS |
|
06/01/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE BACKFLOW PROTECTION FOR VSSI SPRAYERS 2. CHLORINATION DOMESTIC WATER REPORT 3. REPAIR LEAKS UNDER VSSIS 4. PROVIDE DAP ON ALL FIXTURES 5. PROVIDE SUPPORT FOR EXPANSION TANK AT WATER HEATER 6. PROVIDE MED-GAS THIRD PARTY REPORT & TESTING 7. INSTALL ALL MED-GAS OXYGEN AND WAG PER CITY OF TUCSON APPROVED PLANS 8. PROVIDE KEY FOR ROOF LADDER LIST MAY NOT BE COMPLETE |