Permit: T09CM00499

Parcel: 13734001E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/05/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/03/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/01/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/08/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK VDV CABLING
05/07/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/06/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
FINISH VDV CABLING AS PER CODES

OK LIGHTING AND M/C CABLE
05/05/2009 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
04/29/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MC TO BE INDEPENDENTLY SUPPORTED 300.11 - NOT OFF OC CEILING GRID WIRES
2. SECURELY ATTACH FIXTURES TO GRID 410.16
(4 ON CORNERS OR 2 ON CENTERS)
3. SUPPORT VDV CABLING AS PER 300.11, 725.24, 800.24
4. SEAL UNUSED CONDUIT OPENINGS
5. EMT CLAMPS NOT FOR M/C CABLE - USE APPROVED METHODS
04/24/2009 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
04/03/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ALL MAKE UP IN J-BOXES AND MC
2. SUPPORT MC PER CODE AND 6" AND 6' INTERVALS, DO NOT USE EMT CONDUIT AS SUPPORT
3. LV CABLING NOT INSTALLED YET