Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 25 PSI TEST OK LEFT GAS CARD |
|
| 03/18/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE TEE ON PIPING. FUTURE OUTLET ALLOWED ONLY IF SHOWN ON PLAN USE PIPE CLAMPS NOT CONDUIT CLAMPS NOTE: CODE REQUIRES 1/10 PSI INCREMENTATIONS ON TEST GAUGE ALSO, PROVIDE ELECTRICAL BONDING OF GAS LINE. NOTE: IT APPEARS THAT YOUR ELECTRICAL PANEL IS MISSING THE GROUND WIRES |