Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM00466
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/28/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK INSTALL OF RACEWAYS. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 OR LARGER 2. HAVE 1200 AMP RATED SWITCHGEAR WITH 1200 AMP MAIN FEEDING THIS SECTION WITH 150 AMP FROM PV SYSTEM HAVE TOTAL OF 1350 AMPS, THIS VIOLATES NEC 690.64(B) 3. RECALL FOR FINAL WHEN READY |