Permit: T09CM00466

Parcel: 13707047A


Addresses:

101 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM00466

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/28/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/24/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK INSTALL OF RACEWAYS. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 OR LARGER
2. HAVE 1200 AMP RATED SWITCHGEAR WITH 1200 AMP MAIN FEEDING THIS SECTION WITH 150 AMP FROM PV SYSTEM HAVE TOTAL OF 1350 AMPS, THIS VIOLATES NEC 690.64(B)
3. RECALL FOR FINAL WHEN READY