Permit: T09CM00465

Parcel: 134251860


Addresses:

7095 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/19/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) AS BUILTS NEED TO BE BROUGHT THRU PLAN REVIEW FOR FINAL APPROVAL
09/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) COMPLETE ITEMS #1 & #2 FROM INSPECTION ON 9/1/09
09/01/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONE LINE DIAGRAM ON PLAN NOT REFLECTIVE OF FIELD CONDITIONS
2) PROVIDE ACCURATE LOAD CALCULATIONS FOR SERVICE AND PANEL LOADS. LOADS ON PANEL SCHEDULE NOT REFLECTIVE TO LOADS IN FIELD
3) INSTALL DISCONNECTING MEANS FOR LIGHTS PER NEC 410.73
4) EQUIPMENT GROUND ON 30 AMP CIRCUIT TO BE #1O
5) OK EM LIGHTS