Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) AS BUILTS NEED TO BE BROUGHT THRU PLAN REVIEW FOR FINAL APPROVAL |
|
| 09/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEMS #1 & #2 FROM INSPECTION ON 9/1/09 |
|
| 09/01/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONE LINE DIAGRAM ON PLAN NOT REFLECTIVE OF FIELD CONDITIONS 2) PROVIDE ACCURATE LOAD CALCULATIONS FOR SERVICE AND PANEL LOADS. LOADS ON PANEL SCHEDULE NOT REFLECTIVE TO LOADS IN FIELD 3) INSTALL DISCONNECTING MEANS FOR LIGHTS PER NEC 410.73 4) EQUIPMENT GROUND ON 30 AMP CIRCUIT TO BE #1O 5) OK EM LIGHTS |