Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/19/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP MC CABLE WITHIN 12" OF BOXES 2. BOXES WITH 2 MC CABLES IN THEM ARE OVERFILLED NEC 314.16 3. WHY ARE OLD WORK BOXES BEING USED FOR NEW CONSTRUCTION |