Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM00451
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* PLUMBING FINAL OK THIS INSPECTION IS FOR ICE MACHINE ONLY |
|
03/06/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CORRECT BACKPITCH ON ICE BIN DRAIN REMOVE IN LINE VENT ON DRAIN (VENT NOT REQUIRED UNLESS OVER 15') 2. REQUIRE MINIMUM 1" AIR GAP AT FLOOR SINK 3. TRAP TO BE SET TRUE |
|
03/03/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SEPARATE CONDENSATE AND BIN STORAGE DRAINS, WITH P-TRAPS IF OVER 5' IN LENGTH OF APPROVED PRIMED THEN GLUED PVC IF USED, GRAVITY DRAIN TO APPROVED RECEPTOR WITH 1" AIR GAP AS REQUIRED PROPERLY SUPPORTED AND SECURED 2. PROVIDE PROOF OF 1" AIR GAP FOR WATER INLET OR APPROVED BACKFLOW DEVICE WITH CERTIFICATION IF REQUIRED OR LISTING OF PROOF OF CORRECT WATER INLET FOR THIS USE. (THIS INSPECTION FOR ICE MACHINE ONLY) |