Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 08/06/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) INCREASE CONDENSATE DRAIN TO 1" AFTER TEE 2) PROVIDE 1/8" PER FT SLOPE ON CONDENSATE PIPING AND PROVIDE A ROOF JACK AT ROOF PENETRATION 3) PROVIDE PROPER ELECTRIC FITTING AT LOW VOLTAGE CONNECTION TO A/C UNIT 4) PROVIDE REQUIRED GFI SERVICE RECEPT ON THE ROOF |