Permit: T09CM00447

Parcel: 12514021F


Addresses:

3214 E 4TH ST #07

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/14/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/10/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER FLOOR AND WALLS
2) WRAP PIPES WITH FOAM AT CONCRETE
3) SECURE CLOSET FLANGES AND RECALL FOR TUB INSTALL WITH RUN TEST
06/26/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED FITTING FOR ALL PIPING
2) PROVIDE CLEANOUT AT SINK
3) OK TO INSTALL PER UPC 2006 SEC. 908.4
06/18/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT UNDER TEST
06/16/2009 PLUMBING - INTERMEDIATE Cancelled IVRS - RI canceled
06/08/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNIT 7
1. EXPOSE WORK DONE WITHOUT PERMITS
2. CORRECT UPSIDE DOWN SAN T AT TUB
3. CORRECT ABS DIRECTLY EMBEDDED IN CONCRETE

CORRECT:
- LAV TRAP ARM; CAN BE 1 1/2" MAX. AND 42" MAX. LENGTH
- KIT. SINK; WET VENT WOULD REQUIRE A 3" DRAIN
- CLOSET FLANGE; GETS SECURED TO FINISHED FLOOR

UNIT 8 - OK TO COVER
05/19/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE INSP. HISTORY FOR BELOW SLAB PIPING UNIT #7
OR EXPOSE.
WATER PIPING NOT PROPERLY SIZED (BOTH UNITS)
PROVIDE CORRECT USE OF DRAINAGE FITTINGS
PROVIDE PROPER CLEANOUTS
PROVIDE TEST ON NEW PIPING OVERFLOW
PROVIDE TEST ON TUB WATER
SECURE TUB SPOUT
SECURE TUBING
PROVIDE PROPER TRANSITION COUPLING
INSTALL TEMP PLUGS IN ALL OPEN DRAINS