Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/10/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER FLOOR AND WALLS 2) WRAP PIPES WITH FOAM AT CONCRETE 3) SECURE CLOSET FLANGES AND RECALL FOR TUB INSTALL WITH RUN TEST |
|
| 06/26/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED FITTING FOR ALL PIPING 2) PROVIDE CLEANOUT AT SINK 3) OK TO INSTALL PER UPC 2006 SEC. 908.4 |
|
| 06/18/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOT UNDER TEST |
|
| 06/16/2009 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 06/08/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT 7 1. EXPOSE WORK DONE WITHOUT PERMITS 2. CORRECT UPSIDE DOWN SAN T AT TUB 3. CORRECT ABS DIRECTLY EMBEDDED IN CONCRETE CORRECT: - LAV TRAP ARM; CAN BE 1 1/2" MAX. AND 42" MAX. LENGTH - KIT. SINK; WET VENT WOULD REQUIRE A 3" DRAIN - CLOSET FLANGE; GETS SECURED TO FINISHED FLOOR UNIT 8 - OK TO COVER |
|
| 05/19/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE INSP. HISTORY FOR BELOW SLAB PIPING UNIT #7 OR EXPOSE. WATER PIPING NOT PROPERLY SIZED (BOTH UNITS) PROVIDE CORRECT USE OF DRAINAGE FITTINGS PROVIDE PROPER CLEANOUTS PROVIDE TEST ON NEW PIPING OVERFLOW PROVIDE TEST ON TUB WATER SECURE TUB SPOUT SECURE TUBING PROVIDE PROPER TRANSITION COUPLING INSTALL TEMP PLUGS IN ALL OPEN DRAINS |