| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/31/2009 | ELECTRIC - FINAL | Partial Approval | ||
| 08/28/2009 | ELECTRIC - FINAL | Cancelled | CANCELLED PER SUPERVISOR JOSE #668-2307 | |
| 08/28/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/27/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HTRS NOT INSTALLED YET-MUST COMPLY WITH 422.30, 422.31 AND 422.60 2) TRANSFORMERS IN CLOSETS TO COMPLY WITH CITY OF TUCSON ORDINACE #10417 AND 410.8 NEC. MUST HAVE CLEARANCE OF 12" BETWEEN X-FORMER AND NEAREST POINT OF STORAGE SPACE 3) OPEN PANEL COVERS FOR INSPECTION OR HAVE CONTRACTOR ON SITE |
|
| 08/17/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ARC FAULT TO BE ON ALL BEDROOM CIRCUITS PER 210 NEC |