Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/08/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) COMPLETE AIR BALANCE REPORT 2) PROVIDE WORKING INTER LOCK HEAT SENSORS IN HOODS, NO LIFE SAFETY ISSUES OBSERVED, SEE BLDG INSPECTOR FOR TEMP C OF O |
|
| 12/04/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MEANS TO BALANCE SUPPLY REGISTERS 2) EXHAUST FAN INTER LOCK NOT INSTALLED IN TYPE I GREASE HOODS |
|
| 12/02/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*1) D.S.D. TEST OK X 3 2) PROVIDE HEAT SENSOR INTERLOCK ON ALL TYPE 1 HOODS/EXHAUST 3) PROVIDE AIR BALANCE REPORT |