Permit: T09CM00440

Parcel: 132081560


Addresses:

1979 E AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM00440

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2009 ELECTRIC - FINAL Approved
12/09/2009 ELECTRIC - FINAL Approved ALL INSTALLED EQUIPMENT MEETS THE 2005 NEC INSTALLATION STANDARDS FOR ELECTRICAL SYSTEMS.
12/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ELECTRIC PER PLANS AND NEC FOR INSTALLATION
2) UNLISTED EQUIPMENT SUBJECT TO APPROVAL OF ?
12/08/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER FROM ENGINEER FOR COMBINDING GFCI CIRCUITS
2) FINISH PANEL DIRECTORIES AS PREVIOUSLY DISCUSSED
3) NEED ARC FLASH LABEL ON ALL PANELS
4) FINISH EM LIGHTING
5) UNLISTED EQUIPMENT SUBJECT TO APPROVAL OF L. HANLY
12/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) HAVE ENGINEER VERIFY COMBOING OF KITCHEN CIRCUITS INTO ONE CIRCUIT
EXTERIOR:
1) BOND LIGHT POLES AS DISCUSSED
2) USE APPROVED FITTINGS AT DISCONNECT
3) FUSE TO BE SIZED FOR CONDUCTOR AMPACITY
4) FITTING TO BE FOR WET LOCATION
12/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*