Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00440
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2009 | ELECTRIC - FINAL | Approved | ||
12/09/2009 | ELECTRIC - FINAL | Approved | ALL INSTALLED EQUIPMENT MEETS THE 2005 NEC INSTALLATION STANDARDS FOR ELECTRICAL SYSTEMS. | |
12/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC PER PLANS AND NEC FOR INSTALLATION 2) UNLISTED EQUIPMENT SUBJECT TO APPROVAL OF ? |
|
12/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER FROM ENGINEER FOR COMBINDING GFCI CIRCUITS 2) FINISH PANEL DIRECTORIES AS PREVIOUSLY DISCUSSED 3) NEED ARC FLASH LABEL ON ALL PANELS 4) FINISH EM LIGHTING 5) UNLISTED EQUIPMENT SUBJECT TO APPROVAL OF L. HANLY |
|
12/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) HAVE ENGINEER VERIFY COMBOING OF KITCHEN CIRCUITS INTO ONE CIRCUIT EXTERIOR: 1) BOND LIGHT POLES AS DISCUSSED 2) USE APPROVED FITTINGS AT DISCONNECT 3) FUSE TO BE SIZED FOR CONDUCTOR AMPACITY 4) FITTING TO BE FOR WET LOCATION |
|
12/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |