Permit: T09CM00440

Parcel: 132081560


Addresses:

1979 E AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM00440

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/03/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
MAIN SWITCHBOARD:
1) PLEASE VERIFY INSERTS FOR CONDUCTOR PROTECTION 351.42 AND 300.4
2) CABLE BRACING AS PER INSTRUCTIONS
3) NEED LETTER OF TORQUE FOR EQUIPMENT
4) IDENTIFY CONDUCTOR PER 210.5 (C) CITY AMENDMENTS
5) STRAP CONDUCTOR INSULATION FOR TERMINAL CONTACTS
6) SERVICE LATERAL CONDUCTOR NOT PER PLANS OR ENGINEERS REVISED INSTRUCTIONS
7) GROUNDING CONDUCTOR TO BE FREEN ENTIRE LENGTH PER 250.119
8) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FOR PANEL ENCLOSURES
9) A BOND WILL NEED TO BE POSTED FOR POWER
ABOVE CEILING
1) USE APPROVED FITTINGS WITH METAL FLEX
10/08/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/07/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/06/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*