Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM00440
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/03/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* MAIN SWITCHBOARD: 1) PLEASE VERIFY INSERTS FOR CONDUCTOR PROTECTION 351.42 AND 300.4 2) CABLE BRACING AS PER INSTRUCTIONS 3) NEED LETTER OF TORQUE FOR EQUIPMENT 4) IDENTIFY CONDUCTOR PER 210.5 (C) CITY AMENDMENTS 5) STRAP CONDUCTOR INSULATION FOR TERMINAL CONTACTS 6) SERVICE LATERAL CONDUCTOR NOT PER PLANS OR ENGINEERS REVISED INSTRUCTIONS 7) GROUNDING CONDUCTOR TO BE FREEN ENTIRE LENGTH PER 250.119 8) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FOR PANEL ENCLOSURES 9) A BOND WILL NEED TO BE POSTED FOR POWER ABOVE CEILING 1) USE APPROVED FITTINGS WITH METAL FLEX |
|
10/08/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/06/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |